Payne PG80ESA Error Code 13: Limit Circuit Lockout
What Does Code 13 Mean?
Status code 13 on the Payne PG80ESA indicates a limit circuit lockout. This occurs when a limit switch, draft safeguard, flame rollout switch, or blocked vent switch (if used) has been open for longer than 3 minutes. The furnace has shut down completely as a safety measure and will automatically attempt to reset after 3 hours.
The limit switch monitors the temperature inside the furnace. When airflow across the heat exchanger is insufficient, temperatures rise above safe levels and the limit switch opens, cutting off gas to the burners. The blower continues running to dissipate heat. If the overheating condition persists for more than 3 minutes, the furnace enters this lockout state.
The most common cause is a dirty or clogged air filter that restricts airflow through the system. Blocked or closed supply and return vents can also cause overheating. A defective blower motor or capacitor that reduces airflow is another possible cause. If a flame rollout switch has tripped, it may indicate a more serious combustion problem that requires professional attention.
Common Causes
How to Fix It: Replace the Air Filter and Restore Airflow
What You'll Need
- Replacement air filter (correct size for your system) 🛒 Find at FiltersFast · 🛒 Find at Amazon
- Flashlight
Steps
- Turn off electrical power at the breaker and shut off the gas supply valve Locate the furnace circuit breaker and flip it to OFF. Turn the gas shutoff valve to the OFF position (perpendicular to the pipe). If you smell gas, leave immediately and call your gas company.
- Check and replace the air filter Remove the air filter from the return air duct or furnace filter slot. If it is visibly dirty, clogged, or has not been changed in over 3 months, replace it with a new filter of the correct size. Make sure the airflow direction arrow on the new filter points toward the furnace.
- Verify all supply and return vents are open Walk through every room and ensure all supply registers and return grilles are fully open and not blocked by furniture, curtains, or rugs. Even a few closed vents can significantly restrict airflow and cause overheating.
- Inspect the blower area With the power off, look at the blower wheel through the access panel opening. Check for excessive dust buildup on the blower blades, which can reduce airflow. Also verify the blower wheel is securely attached to the motor shaft and not wobbling.
- Restore power and gas, then test Turn the gas supply valve to ON and flip the circuit breaker to ON. The furnace may need up to 3 hours to auto-reset from lockout, or you can reset it by cycling the power (turn off for 30 seconds, then back on). Set your thermostat to call for heat and monitor the furnace through its heating cycle.
When to Call a Professional
Contact a licensed HVAC technician if:
- Code 13 returns after replacing the filter and opening all vents
- The blower motor does not seem to be running at full speed or makes unusual noises
- The flame rollout switch has tripped (a red button on the switch needs manual reset)
- The blower wheel is loose, damaged, or excessively dirty
- The problem occurs repeatedly even with a clean filter
Sources
✓ Verified against manufacturer service manual — March 2026