Error Code 31
High

Bryant 340MAV Error Code 31: Pressure Switch Did Not Close or Reopened

TL;DR
Your Bryant 340MAV's pressure switch failed to close or reopened, indicating a venting or draft problem. Check for blocked exhaust vents, a clogged condensate drain, and obstructed combustion air intake.
Disclaimer
This article is for informational purposes only and does not guarantee the accuracy or completeness of the information provided. Always turn off power and gas supply before attempting any repairs. If you smell gas, leave immediately and call your gas company. Consult a licensed HVAC technician for diagnosis and repair. Any actions taken based on this information are at your own risk.

What Does Code 31 Mean?

Status code 31 on the Bryant 340MAV indicates that the pressure switch did not close or reopened during operation. The pressure switch is a safety device that verifies the inducer motor is creating enough draft to safely vent combustion gases out of your home before the burners are allowed to fire.

If the pressure switch remains open for longer than five minutes, the inducer shuts off for 15 minutes before the control retries. This cycle will continue until the problem is resolved. The 340MAV is a direct-vent condensing furnace, meaning it draws combustion air from outside through a dedicated intake pipe and exhausts through a separate vent pipe — both must be clear for the pressure switch to close.

The most common cause is a blocked or restricted exhaust vent or combustion air intake pipe. Snow, ice, leaves, bird nests, or insect nests can block the vent pipes where they exit your home. On a condensing furnace, a clogged condensate drain can also cause water to back up into the inducer and prevent the pressure switch from closing. Other possible causes include disconnected or obstructed pressure tubing, excessive wind, low inducer voltage, and a defective pressure switch.

Common Causes

Cause Likelihood DIY?
Blocked or restricted exhaust vent Most common ✓ DIY fix →
Disconnected or obstructed pressure tubing Common ✗ Call a pro →
Excessive wind affecting vent Common ✗ Call a pro →
Inadequate combustion air supply Common ✓ DIY fix →
Defective pressure switch or connections Uncommon ✗ Call a pro →

How to Fix It: Clear Vent Blockages and Check Condensate Drain

⚠ Safety First
Always turn off the furnace at the power switch or breaker and shut off the gas supply before beginning. Do not proceed if you smell gas — leave the area and call your gas company immediately.

What You'll Need

Steps

  1. Turn off electrical power at the breaker and shut off the gas supply valve Locate the furnace circuit breaker and flip it to OFF. Turn the gas shutoff valve to the OFF position (perpendicular to the pipe). If you smell gas, leave immediately and call your gas company.
  2. Inspect the exhaust vent and combustion air intake outside Go outside and locate where the furnace exhaust vent and combustion air intake pipe exit your home (typically PVC pipes on an exterior wall). Check for any blockages such as snow, ice, leaves, bird nests, insect nests, or other debris. Clear any obstructions you find. Make sure the vent terminations are not buried in snow or pressed against a wall or shrub.
  3. Check the condensate drain Locate the condensate drain line — a small PVC pipe that carries water away from the furnace. Check if water is backing up or if the drain is clogged. If accessible, try clearing the drain by pouring warm water through it or using a wet/dry vacuum on the drain outlet. Also check the condensate trap if your furnace has one — it may be full of debris.
  4. Inspect the visible vent piping inside Look along the vent pipes from the furnace to where they exit the building. Check for any obvious sagging sections where water could collect, disconnected joints, or damage. Do not disassemble the vent piping — just note any problems.
  5. Restore power and gas, then test Turn the gas supply valve to ON and flip the circuit breaker to ON. Set your thermostat to call for heat and monitor the furnace. Listen for the inducer motor to start and watch for the ignition sequence to complete successfully.
How to Verify
The furnace should complete a full heating cycle without code 31 reappearing. You should hear the inducer motor running steadily before and during the heating cycle. If the code returns, especially on windy days, there may be a vent sizing or wind-related issue that requires professional assessment.

When to Call a Professional

Contact a licensed HVAC technician if:

🔧 Find an HVAC Pro Near You
Compare quotes from HVAC pros in your area. Free quotes, no obligation.
Get Free Quotes
We earn a referral fee when you connect with a service provider through this link.

Sources

  1. Bryant 340MAV J Series Service and Maintenance Procedures Manual

✓ Verified against manufacturer service manual — March 2026