Bryant 340MAV Error Code 31: Pressure Switch Did Not Close or Reopened
What Does Code 31 Mean?
Status code 31 on the Bryant 340MAV indicates that the pressure switch did not close or reopened during operation. The pressure switch is a safety device that verifies the inducer motor is creating enough draft to safely vent combustion gases out of your home before the burners are allowed to fire.
If the pressure switch remains open for longer than five minutes, the inducer shuts off for 15 minutes before the control retries. This cycle will continue until the problem is resolved. The 340MAV is a direct-vent condensing furnace, meaning it draws combustion air from outside through a dedicated intake pipe and exhausts through a separate vent pipe — both must be clear for the pressure switch to close.
The most common cause is a blocked or restricted exhaust vent or combustion air intake pipe. Snow, ice, leaves, bird nests, or insect nests can block the vent pipes where they exit your home. On a condensing furnace, a clogged condensate drain can also cause water to back up into the inducer and prevent the pressure switch from closing. Other possible causes include disconnected or obstructed pressure tubing, excessive wind, low inducer voltage, and a defective pressure switch.
Common Causes
How to Fix It: Clear Vent Blockages and Check Condensate Drain
What You'll Need
Steps
- Turn off electrical power at the breaker and shut off the gas supply valve Locate the furnace circuit breaker and flip it to OFF. Turn the gas shutoff valve to the OFF position (perpendicular to the pipe). If you smell gas, leave immediately and call your gas company.
- Inspect the exhaust vent and combustion air intake outside Go outside and locate where the furnace exhaust vent and combustion air intake pipe exit your home (typically PVC pipes on an exterior wall). Check for any blockages such as snow, ice, leaves, bird nests, insect nests, or other debris. Clear any obstructions you find. Make sure the vent terminations are not buried in snow or pressed against a wall or shrub.
- Check the condensate drain Locate the condensate drain line — a small PVC pipe that carries water away from the furnace. Check if water is backing up or if the drain is clogged. If accessible, try clearing the drain by pouring warm water through it or using a wet/dry vacuum on the drain outlet. Also check the condensate trap if your furnace has one — it may be full of debris.
- Inspect the visible vent piping inside Look along the vent pipes from the furnace to where they exit the building. Check for any obvious sagging sections where water could collect, disconnected joints, or damage. Do not disassemble the vent piping — just note any problems.
- Restore power and gas, then test Turn the gas supply valve to ON and flip the circuit breaker to ON. Set your thermostat to call for heat and monitor the furnace. Listen for the inducer motor to start and watch for the ignition sequence to complete successfully.
When to Call a Professional
Contact a licensed HVAC technician if:
- The exhaust vent and intake appear clear but code 31 persists
- You cannot access or clear the condensate drain
- The inducer motor sounds unusually loud or does not start at all
- You see water pooling around the furnace base
- The code occurs only on windy days (may indicate improper vent termination or sizing)
✓ Verified against manufacturer service manual — March 2026